DURAG D-LX 200 UA-20/87Ex flame monitoring device

  • Power plants
  • Refineries
  • Chemical facilities
  • Cement plants
  • Waste incinerators
  • Continuous combustion processes
  • Hazardous areas (Ex zones)
  • You can become a member here to see prices and take advantage of other privileges.
    The DURAG D-LX 200 UA-20/87Ex is a compact flame monitor operating in the UV spectrum, designed for hazardous areas with Ex protection. It measures flame flicker frequency and intensity to ensure reliable flame detection. The device supports SIL3 safety level and offers remote monitoring via Modbus RTU and IrDA.
  • Spectral sensitivity: 190 – 520 nm (UV)
  • Power supply: 24 VDC ±20%
  • Power consumption: 5 W
  • Operating temperature: -40°C to +85°C
  • Protection class: IP66/IP68
  • Flame relay: 1x NO contact, 24 VDC, 0.5 A
  • Status relay: 1x NO contact, 24 VDC, 0.5 A
  • Analog output: 0/4...20 mA
  • Safety time: 1, 2, 3, 5 seconds
  • Communication: Modbus RTU, IrDA
  • Mounting: G 1¼” or 1¼” NPT(F) connection
  • Ex protection: ATEX certified (suitable for Zone 1 and 21)